Max. flow 85 l/min
Max. operating pressure 68 bar
Minimum line pressure 350mb
Proof pressure 100 bar
Temperature range – with Polysulfone piston (standard), with cable, with
plug connector: -20°C…+80°C
– with metal piston and terminal box: -20°C…+150°C
Adjustment range 2…75 (l/min)
Switching function
(related to increasing flow) -NC, NO, SPDT
Mounting orientation any position
Factory calibration position horizontal, electrical connection up
Repeatability ±1%
Adjustment accuracy ±10%
Hysteresis max. 15%
Mounting G 1/2″
Electrical connections – cable: PVC, 2 or 3 x 0.34 mm2
(length: approx. 1m)
– plug connector per DIN 43650
– terminal box
Enclosure – IP 65
Electrical data contact rating – SPST (NC/NO): 100 VA, 3 A, 220 V~
– SPDT 20 VA, 0.5 A, 250 V~
Weight 1.2 kg
Filtration 50 microns